DTSk2(EOL)

$0.00

End Of Life Product (See CVM-A1500)

Power Quality Analyzer / Submeter

  • Ethernet and RS-485 connectivity
  • Modbus TCP and Modbus RTU
  • On-board SD memory card for logging
  • One display can monitor up to 32 meter modules
  • Expansion slots for optional digital and analog I/O
  • Voltage and current harmonics up to 50th
  • Graphic LCD, back-lit display
  • Calculation of THD, Waveform displays

Data Sheets & Downloads

DTSk2 Brochure (2.2 Mb) [PDF]

Product Description

The DTSk2 measures, calculates and displays the primary electric parameters in balanced or unbalanced three-phase industrial networks. True rms values are measured using three alternating voltage inputs, two voltage references (neutral and ground), and four current inputs to measure secondaries 1A or 5A, coming from the outside current transformers. It should be considered that when secondary 1A is selected, the calculation is made by the software.

The DTSk2 network and power supply quality analyzer is a programmable measuring instrument. It offers a wide variety of uses, which can be selected from the instrument’s configuration menus. Prior to using the analyzer, read the following sections carefully: power supply, connection and configuration. Then, choose the best operating method for obtaining the desired data. The DTSk2 permits viewing the electric parameters on a backlit 1/4 vga graphical display. real time, maximum or minimum electric parameters can be viewed by pressing the corresponding key. The DTSk2 internal processor shows more than 500 electric parameters via the display screen and communication; these parameters may be fed from a single or three phase system.

Features

Features

  • Over 500 electrical parameters displayed
  • On-board SD memory card for logging (up to 2GB)
  • One display can monitor up to 32 meter modules
  • Display can be mounted separately from meter module
  • Flexible communications capabilities (Modbus TCP, RS485 with Modbus protocol, PROFIBUS)
  • 3 expansion slots for optional digital and analog I/O
  • Incorrect connection detection
  • Flexible mounting options including 4” round ANSI, 96x96mm, 144x144mm as well as DIN rail
  • 300 x 240 pixel (1/4 VGA) graphic LCD, back-lit display
  • Waveform displays
  • 4 quadrant measurements
  • Universal AC/DC power supply
  • Compatible with PowerStudio™ Energy management and control software suite

Energy Meter

  • ANSI C12.20 Class 0.5 Energy Meter (class 0.2 also available)
  • Up to 9 TOU (time of use) tariffs
  • kW, kVA and Current Demand
  • Maximum Demand displayed with time stamp

Power Quality Analyzer

  • Detection of sags, swells, interruptions and disturbances
  • Flicker (PST) according to IEC 61000-4-15 standard
  • Calculation of unbalance and asymmetry according to IEC 61000-4-30
  • Voltage and current harmonics up to 50th
  • Harmonic distortion for Voltage and Current
  • Calculation of THD using the fundamental or RMS

Communication Capabilities

  • Ethernet Modbus TCP/RTU and Modbus TCP
  • RS-485 with Modbus RTU and Modbus TCP
  • Compatible with PowerStudio Energy management and control software suite
  • Up to 3 communications expansion slots
  • DTSK2trans

Display Features

  • Incorrect connection detection
  • Internal clock for setting of 12 hourly tariffs (TOU)
  • Menu system with soft keys
  • Direct access to measurement screens, setup etc.
  • Access to summary of system by key function (PT, CT, registry etc.)
  • Menus in different languages
  • Large 300×240 pixel graphic, back-lit LCD display
  • Default page – user defined

Expansion slots

  • Each meter has up to 3 expansion slots available
  • Ethernet connectivity
  • SD memory card slot
  • 8 mechanical inputs and 4 mechanical relay outputs
  • 8 static digital inputs and 8 static digital outputs
  • 4 analog inputs and 4 analog outputs

Specifications

Voltage Inputs

Measurement range: 5 to 120% Un (300 V ac L-N / 520 V ac L-L)
Frequency: 45 to 65Hz S
Maximum measured voltage: 360 V ac
Over voltage allowance: 750 V ac
Consumption: <0.6 VA Output range: 4000

Current Inputs

Minimum measured current: 20 mA
Measurement range: 1 to 120% In (In = 5 A)
Secondary CT: (In) 1 or 5 A
Primary current: Programmable <30000 A
Excess load admitted: 6A permanent ; 100 A t<1 s
Consumption: <0.45 VA

Auxiliary Supply

Power supply:
80 to 265 V ac (50-60Hz) (consumption <30 VA)
90 to 300 V dc (consumption <25W)

Accuracy

Type 54-2
Currents: (I) ± 0.2% 10% to 120% In
Voltage: (V) ± 0.2% 20% to 120% Un
Active power P: ± 0.2% 10% to 120% In
Reactive power Q: ± 0.5% 10% to 120% In
Apparent power S: ± 0.5% 10% to 120% In
Frequency F: ± 0.01 Hz 45 to 65 Hz
Active energy: ± 0.2 %
Reactive energy: ± 0.5 %
Apparent energy: ± 0.5 %

Type 54-5
Currents: (I) ± 0.5% 10% to 120% In
Voltage: (V) ± 0.5% 20% to 120% Un
Active power P: ± 0.5% 10% to 120% In
Reactive power Q: ± 1.0% 10% to 120% In
Apparent power S: ± 1.0% 10% to 120% In
Frequency F: ± 0.01 Hz 45 to 65 Hz
Active energy: ± 0.5%
Reactive energy: ± 1.0%
Apparent energy: ± 1.0%

Digital Pulse Outputs

Type: Optocoupler
Operating voltage: 24 V dc
Maximum power: (per output) 0.8 W
Maximum Ron: 35 ohms

Digital Relay Outputs

Type: Mechanical relay
Operation voltage: 250 V ac
Max current: (resistive load) 3A

Digital Inputs

Type: Voltage free
Coupling: Optically isolated
Max. peak voltage: 24Vdc
Minimum times: ton = 40msecs, toff = 40msecs

Analog Outputs

Scale: 0 to 20 mA or 4 to 20 mA
Maximum allowed load: 500 Ω
Response time: < 2 s
Output range: 4000

Analog Inputs

Type: Current
Rated input range: 0/4 – 20mA
Measurement precision: 1%
Input Impedance: 200 Ω

Communications

Type: RS-485
Protocol: Modbus / RTU
Speed: (configurable) 9600, 19200, 38400, 57600 baud
Parity: odd, even or no parity
Stop bits: 1 or 2

Ethernet Communications

Type: Ethernet – RJ45
Protocol: Modbus / TCP
Speed: 10 base T / 100baseT

Environment

Operation temperature: 14°F to 122°F (-10 to + 50 °C)
Storage temperature: -4°F to 149°F (-20 to + 65 °C)
Relative humidity: 95% without condensation
Installation category: CAT III according to IEC 61010
Level of contamination: 2 according to IEC 61010
Protection index: IP51 front, IP20 rear section

Mechanical

Connection: Screw terminal block up to 10 10 AWG (4.5mm2)

Regulation References

EMC: 61000-4-2, 61000-4-3, 61000-4-11, 61000-4-4, 61000-4-5
UL Listed: File # NMTR.E227534

Add-On Products