The DTS 307 MCM Series of multi-circuit monitors has been designed to provide a single metering solution for 9, 12, 18 or 24 branch circuits (3, 4, 6 or 8 Three phase circuits).
The series is based on the ultra-compact DTS 307 3 channel 208V-480V sub-meter.
It is offered in 2 formats:
Pre-wired with 1.5ft voltage pigtails on a DIN rail to be mounted into a 3rd party enclosure
Wall-mounting, non-metallic weatherproof enclosure adder with voltage terminals or fuses.
It is available with serial or ethernet communications with Modbus or BACnet protocols
The DTS 307 can be configured to operate as a Bi-directional NET meter. The DTS 307 is SunSpec Alliance certified and easily integrates with Building Automation Systems and Energy Monitoring Software. All the DTS Series is designed and manufactured in the USA and complies with the Buy American Provisions of ARRA Section 1605.
Features
Line powered single / three phase energy sub-meter
Auto-topology detection
Ultra-Compact DIN rail design
UL Listed, CE, FCC Part 15 Class B
ANSI C12.20 – “Revenue grade”
BTL Listed, SunSpec Alliance certified
208-480 Vac (1P 2W, 1P 3W, 3P 4W)
RS-485 connectivity – Modbus RTU and BACnet MS/TP (field selectable)
Ethernet connectivity – Modbus TCP and BACnet/IP
Interfaces with 333mV or Rogowski CTs (field selectable)
Bi-directional for renewable systems (NET metering)
Color coded, pluggable connectivity
User configurable using DTS Config software
User-definable Modbus register area
Optional Low Voltage AC/DC Auxiliary (12-24Vdc or 24Vac)
Optional single Pulse Output (kWh)
kWh (Active Energy) Counter Display option
Designed and Manufactured in the USA.
Complies with the Buy American Provisions of ARRA Section 1605
Also available in a OEM board level format
Specifications
Measuring Circuits
Voltage range: 208-480Vac, L-L (CAT III)
120-277Vac L-N (CAT III)
Voltage overload: 1.1 x
Voltage burden: <0.1 VA @ 277 Vac L-N
Frequency: 45 to 65 Hz
Rated current: 333mV or model dependent
Current overload: 1.2 x
Power overload: 1.2 x
Accuracy
Voltage: 0.5%, <0.2% typical (80-120%)
Current: 0.5%, <0.2% typical (10-120%)
Power: 0.5%, <0.2% typical (10-120%)
Power Factor: 0.5% (between 0.5 and 1.0)
Energy:** Class 0.2 (ANSI C12.20)
Voltage Supply (Self Powered)
Voltage: Powered from Phase A & Neutral (model dependent)
Frequency: 50/60 Hz
Burden: <2VA
Low Voltage Auxiliary (Option)
Voltage options: 12-24Vdc or 24Vac
Tolerance: +/- 10%
Burden: <2VA
Isolation: Must be powered from a Class 2 IEC 60950 isolated power supply
Mechanical Connection
Pluggable screw terminals suitable for 12AWG stranded wire (2.5mm2)
Case Material: Self-extinguishable, V0 plastic
Protection: Nema 1 (IP40)
Dimensions of DTS 307: 3.11”(79mm) H x 3.11”(79mm) D x 1.38”(35mm) W
Weight: 0.5lb (0.23 kg)
Environmental
Operating temp: -4º to 158ºF (-20º to 70ºC)
Storage temp: -40º to 185ºF (-40º to 85ºC)
Humidity: 5 to 95% R.H. non-condensing
Communications (Serial)
Connection: 3 way pluggable, screw terminal
Protocols: Modbus RTU (SunSpec Certified) or BACnet MS/TP (BACnet Listed)
Pulse Output
Type: Potential Free, N.O. Solid State Relay
Pulse Width: Max 10 Pulses per Second
Pulse Rate: 1 Pulse / 1 KWh default, user configurable
Max On-Resistance: 30 ohm
Max switching voltage: 50Vdc or 30Vac
Max switching current: 120mA (350mA for 10mS)
Connection: Isolated Pin-Pair
Standards & Safety
UL listing: E488290
Conforms to: UL Std 61010.1 3rd Edition, May 11, 2012,
Revised July 15, 2015
Certified to: CAN/CSA C22.2 # 61010.1, 3rd Edition,
Revised July 15, 2015
Additional Standards: IEC 61010-2-030: 2010, 1st Edition
EMC: IEC 61326-1 (2012) Ed2.
IEC 61000-3-2, IEC 61000-3-3, IEC 61000-4-2,
IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5,
IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
Emissions: CISPR 11 Group1 Class B / FCC Part 15 Class B
Other: Measurement Category III – 300Vac L-N / 520Vac L-L
Communications: BTL Listed, SunSpec Alliance certified
RoHS: compliant